Fault outputs
7.2 Fault outputs
If a flowmeter failure occurs, transmitters produce fault outputs. Model
RFT9739, IFT9701, IFT9703, RFT9712, and RFT9729, produce
downscale or upscale outputs to indicate a fault. In addition, a Version 2
or earlier RFT9739 also has last measured value and internal zero fault
levels.
• To set downscale or upscale fault output levels for a Version 3
RFT9739, an IFT9701, an IFT9703, an RFT9712, or an RFT9729,
refer to the transmitter instruction manual.
• To set fault levels for a Version 2 or earlier RFT9739, open the
Configure menu, then choose Transmitter Outputs.
RFT9739
• Downscale: milliamp outputs go to 0 mA if they produce a 0-20 mA
current, or to 0-2 mA if they produce a 4-20 mA current;
frequency/pulse output goes to 0 Hz.
• Upscale: milliamp outputs go to 22-24 mA; frequency/pulse output
goes to 15-19 kHz.
• Last measured value (not available with Version 3 transmitters):
Outputs hold the values measured immediately before the fault
condition occurred.
• Internal zero (not available with Version 3 transmitters): Outputs
indicate a value of zero for the represented process variable.
IFT9701/IFT9703
• Downscale: The milliamp output goes to 2 mA; the pulse output goes
to 0 Hz.
• Upscale: The milliamp output goes to 22 mA; the pulse output goes
to 7200 Hz for version 1.2 and higher or 1200 Hz for lower versions.
RFT9712/RFT9729
• Downscale: The milliamp output goes to 2 mA; the frequency/pulse
output goes to 0 Hz.
• Upscale: The milliamp output goes to 22 mA; the frequency/pulse
output goes to 11,520 Hz.
7.3 Critical indicators
Critical indicators switch ON under the following conditions:
• Master reset defaults in transmitter software
• Transmitter failure
• Flow, temperature, or density outside sensor limits
• Faulty flowmeter wiring, cable, or connections
• Inappropriate density calibration factors
• Plugged or partially plugged flow tubes
• Loss of input signal (when pressure is enabled)
• Temperature calibration failed (RFT9712 and RFT9729 only)
• Data loss during configuration